BathSelect® Smart Showers — Series‑Specific Technical Appendix (Digital Mixing & Controls)
Engineering planning data for BathSelect® Smart Showers: digital mixing valves, multi‑outlet diverters, and smart controllers used in hospitality, residential luxury, wellness, education, healthcare, and civic facilities.
Planning values below are typical design targets for driver sizing, wiring, hydraulics, torque, and commissioning. For stamped submittals, always use the latest cut sheet, BIM (.RFA), CSI, and wiring diagrams for your exact SKU and jurisdiction.
1) Model Families & Roles
1.1 Smart Controllers (User Interface)
|
Model
|
Power
|
Interfaces
|
IP Rating
|
Setpoints
|
UI & Features
|
Notes
|
|
Pulse™ Controller
|
12 VDC (SELV), 4 VA
|
BLE (local), Dry‑contact input (occupancy)
|
IP65 (behind panel)
|
80–120 °F (27–49 °C), default 104 °F (40 °C), limit 120 °F
|
Glass/metal touch UI; 4 presets; pause; warm‑up; auto‑off 15–30 min
|
Mount outside direct spray; low‑glare backlight
|
|
Sync™ Controller
|
12 VDC, 5 VA
|
BLE + optional RS‑485 service port
|
IP65
|
80–120 °F; limit 115–120 °F policy
|
6 presets; outlet icons; maintenance lock
|
Good for hotels & spas
|
|
Nexus™ Controller
|
12–24 VDC, 6 VA
|
BLE + BACnet/Modbus (gateway)
|
IP65 (controller), Gateway in ELV closet
|
70–120 °F (21–49 °C), facility bands per role
|
8 presets; usage counters; cleaning mode
|
Network‑aware with gateway (optional)
|
1.2 Digital Mixing Valves (DMV)
|
Model
|
Inlets/Outlets
|
Size & Threads
|
Cv (approx.)
|
Max Flow*
|
Fail‑Safe
|
Compliance
|
Sensors
|
|
HydroMix™ 2P
|
H/C → 1 outlet
|
1/2" NPT (F) in/out
|
2.5
|
8 gpm @ 45 psi
|
Hot/cold fail‑close; power‑off close
|
ASSE 1016; ASME A112.1016
|
Dual thermistors; flow; valve pos.
|
|
HydroMix™ 3P
|
H/C → 1 outlet + 3‑port diverter bus
|
1/2" NPT (F)
|
2.5
|
8 gpm @ 45 psi
|
Same as above
|
ASSE 1016
|
As above + diverter sense
|
|
QuadraMix™ 4P
|
H/C → 2–4 outlets via smart diverter
|
3/4" NPT (F) in/out
|
4.0
|
12 gpm @ 45 psi
|
Same as above
|
ASSE 1016 / 1069 (multi‑user)**
|
Dual thermistors; flow; valve pos.
|
*Flow subject to local max‑flow rules and outlet devices (1.75–2.5 gpm typical shower heads).
**Use ASSE 1069 guidance for gang/accessible group showers; use ASSE 1017 at plant for master tempering if applicable.
1.3 Smart Diverters & Outlet Modules
|
Model
|
Outlets
|
Threads
|
Power
|
Notes
|
|
FlowHub™ 2
|
2
|
1/2" NPT (F)
|
12 VDC, 3 VA
|
Auto‑purge between outlet changes; anti‑hammer ramp
|
|
FlowHub™ 4
|
4
|
1/2" NPT (F)
|
12 VDC, 5 VA
|
For rain, handshower, body jets, tub; interlock logic
|
2) Electrical — VA, Drivers & Wiring
2.1 Per‑Unit VA (peak) & Recommended Driver (per set)
|
Configuration
|
DMV (VA)
|
Diverter (VA)
|
Controller (VA)
|
Driver per set (min)
|
Notes
|
|
HydroMix 2P + Pulse
|
10
|
—
|
4
|
20 VA
|
Single‑outlet digital shower
|
|
HydroMix 3P + FlowHub 2 + Sync
|
10
|
3
|
5
|
25–30 VA
|
Two outlets (e.g., rain + handshower)
|
|
QuadraMix 4P + FlowHub 4 + Nexus
|
15
|
5
|
6
|
35–40 VA
|
Up to four outlets; gateway optional
|
Bank sizing:
with Simultaneity 0.5–0.7 typical + 20–30% headroom. Keep voltage drop ≤ 5% (≤0.6 V on 12 V). Use star topology; 18 AWG typical; upgrade to 16 AWG for long runs.
2.2 Cabling & EMC
-
LV control cables: 18–22 AWG copper; separate from mains and hand dryer feeds.
-
In high‑EMI zones (VFDs), use shielded LV cable; bond shield per wiring diagram; add ferrites if needed.
-
Never share conduits with mains; label polarity and node IDs.
3) Mechanical — Threads, Torque & Mounting
3.1 Valve & Diverter Torques
|
Component
|
Connection
|
Torque (N·m)
|
Notes
|
|
HydroMix 2P/3P union nuts
|
1/2" NPT to union
|
20–27
|
Use thread sealant/PTFE per code; do not over‑torque
|
|
QuadraMix 4P union nuts
|
3/4" NPT to union
|
27–35
|
Support piping to avoid valve strain
|
|
FlowHub diverter unions
|
1/2" NPT
|
18–24
|
Ramp‑open programming reduces hammer
|
|
Controller mounting
|
Panel screws
|
0.6–0.9
|
Do not crush gasket; IP integrity
|
3.2 Pressure & Temperature
-
Operating pressure 20–80 psi; PRV above 80 psi; arrestors on aggressive mains.
-
Setpoint band 70–120 °F (21–49 °C); default 104 °F (40 °C); limit 115–120 °F per policy.
-
Thermal disinfection: 140–158 °F (60–70 °C) supervised for 2–5 min.
3.3 Plumbing Notes
-
Isolate with full‑port ball valves; install checks on H/C inlets; use service strainers.
-
For recirculated systems, follow loop balancing and anti‑dead‑leg practices; position DMV close to outlets.
4) Commissioning — Step‑by‑Step
-
Pre‑flush hot and cold lines; clean strainers; verify water quality.
-
Verify pressure 20–80 psi and supply temperature ranges.
-
Mount DMV and diverter; torque per §3.1; leak test at working pressure.
-
Wire SELV driver; star topology; verify polarity; label nodes.
-
Connect controller; update firmware if prompted (service app).
-
Program setpoint limits, max run (15–30 min), cleaning/housekeeping mode.
-
Run auto‑calibration (thermistors/valve position); verify stable 104 °F output @ typical flow.
-
Test fail‑safe: close hot, confirm DMV shuts; close cold, confirm DMV shuts; remove power, confirm close.
-
Exercise outlet switching; check anti‑hammer ramps and cross‑flow isolation.
-
If recirc present, verify warm‑up/purge routine and return temps.
-
Document settings; export BLE snapshot (where supported); hand over O&M sheet.
5) Hygiene & Disinfection Routines
-
Warm‑up: Pre‑use flush to reach setpoint before enabling user control.
-
Hygiene flush: 10–30 s after chosen idle window (facility policy).
-
Thermal purge: 60–70 °C (140–158 °F) for 2–5 min, supervised; auto‑revert to tempered; signage/area control required.
-
Auto‑purge between outlets to clear stagnant branches on diverter change.
6) Controls & BMS Integration
-
Local BLE commissioning; store non‑PII counters (uses, runtime).
-
Optional gateway enables BACnet/IP or Modbus TCP (read: temps, valve pos., status; write: enable/disable, presets, cleaning mode).
-
Use role‑based setpoint bands (e.g., guest 95–109 °F, spa 95–112 °F, accessible 90–105 °F).
-
Log faults (sensor open/short, over‑temp, supply fail) to CMMS.
7) Troubleshooting (Quick Matrix)
|
Symptom
|
Likely Cause
|
Corrective Action
|
|
Temperature hunts
|
Unbalanced H/C pressure, fouled strainers
|
Balance supplies; clean strainers; re‑calibrate DMV
|
|
Low flow
|
Outlet restrictor, low supply, debris
|
Verify outlet gpm; check PRV; clean checks/strainers
|
|
Outlet cross‑flow
|
Diverter seat debris
|
Run valve seat clean cycle; inspect diverter
|
|
No response / resets
|
LV noise, voltage drop
|
Shorten runs; use 16–18 AWG; separate from mains; ferrite chokes
|
|
Over‑temp trip
|
Setpoint limit exceeded or sensor fault
|
Verify sensors; confirm limit policy; thermal test
|