BathSelect® Aero Series — Technical Specifications & Advanced FAQ
Aero Series · Technical Data

BathSelect® Aero Series — Technical Specifications & Advanced FAQ

Detailed, spec‑grade information for Zephyr™, Vortex™, Jetstream™, Stratus™, Cyclone™, Nimbus™. Values below represent typical design targets; confirm the latest cut sheets, BIM families, and wiring diagrams for the exact SKU and jurisdiction.

On this page

Downloads

Links are clean placeholders — replace with live CMS asset URLs when available.

Zephyr™ — Technical Specifications

CategorySpecification
Faucet Flow Options0.35 gpm (laminar) · 0.5 gpm (laminar/aerated), pressure‑compensated
Operating Pressure20–80 psi (recommended); PRV above 80 psi
Inlet Threads3/8" compression (NPSM) braided hoses, 24" typical
Electrical — Battery6 V nominal (4×AA); latching solenoid; standby < 100 µA; pulse 0.6–0.9 A / 40–80 ms
Electrical — AC/Driver100–240 VAC → SELV 12 VDC; ≥15 VA per device (≥30 VA per set)
Wiring Runs18–22 AWG; max 15 m at 18 AWG; dedicated low‑voltage homeruns
Mounting & TorqueDeck 15–40 mm; faucet shank nut 6–8 N·m; dispenser collar 2–3 N·m; escutcheon screws 1.0–1.5 N·m
SensorNarrowband IR with ToF assist; adjustable range ~80–120 mm; reflective‑surface compensation
Hygiene Flush12/24/48/72 h idle → run 3–8 s
Thermal Purge60–70 °C for 2–5 min (maintenance); supervise; coordinate with ASSE 1070 mixing
DispenserLiquid 1–3000 cP; 1000 mL tank; dose 0.8–1.5 mL; anti‑drip; purge/prime
Materials/FinishLead‑free brass body; Chrome or PVD (Brushed Nickel, Matte Black, Brushed Gold)
EnvironmentElectronics IP65; ambient 0–50 °C; RH 5–95% non‑condensing
ComplianceDesign intent: ASME A112.18.1/CSA B125.1; NSF/ANSI 61/372; ADA/ICC A117.1 planning

Vortex™ — Technical Specifications

CategorySpecification
Faucet Flow Options0.35/0.5 gpm (pressure‑compensated); vandal‑resistant outlet
Operating Pressure20–80 psi; fit hammer arrestors for aggressive mains
Inlet Threads1/2" NPSM braided hoses, 24" typical
Electrical — Battery6 V (4×AA); standby < 120 µA; pulse 0.7–1.0 A / 60–90 ms
Electrical — AC/DriverSELV 12 VDC; recommend 20 VA per device in high‑traffic venues
Wiring Runs18 AWG up to 20 m; shielded cable recommended where EMI present
Mounting & TorqueDeck 15–45 mm; shank nut 8–10 N·m; dispenser collar 3–4 N·m; anti‑rotation gasket included
Hygiene Flush24/48/72 h idle → run 4–10 s; obstruction lockout 30–90 s
Thermal Purge60–70 °C for 3–5 min; supervised; area control
DispenserLiquid; 1000 mL; 0.8–1.5 mL dose; anti‑drip; vandal shield bezel
EnvironmentIP65 electronics; abrasion‑resistant bezels; cleaning‑chemical tolerant (avoid bleach)

Jetstream™ — Technical Specifications

CategorySpecification
Faucet Flow Options0.35/0.5 gpm with integrated touchless mixing (ASSE 1070 compatible)
Operating Pressure20–80 psi; maintain balanced hot/cold feeds
Inlet Threads3/8" compression (hot/cold) + 3/8" outlet to spout/manifold
Electrical — AC/DriverRequired SELV 12–24 VDC; faucet 8 VA typical (peaks 12 VA); dispenser 6 VA typical — size 25–30 VA per set
Electrical — BatteryNot recommended for mixer SKU due to duty cycle
ConnectivityOptional BLE 4.2/5.0 for local commissioning & snapshot export (settings/counters); no cloud required
Wiring Runs18 AWG up to 20 m; observe polarity; avoid sharing conduit with mains
Mounting & TorqueDeck 15–40 mm; faucet shank nut 6–8 N·m; mixer manifold screws 2.0 N·m; dispenser collar 2–3 N·m
Hygiene FlushIdle 12/24/48 h; 3–8 s; programmable via service mode/BLE
Thermal Purge60–70 °C for 2–4 min; manual enable only; auto‑revert to tempered
DispenserLiquid; 1000 mL; 0.8–1.5 mL dose; anti‑drip; purge/prime
EnvironmentIP65; ambient 0–50 °C

Stratus™ — Technical Specifications

CategorySpecification
Faucet Flow Options0.35/0.5 gpm (laminar outlet recommended for healthcare)
Operating Pressure20–80 psi; flush lines prior to commissioning
Inlet Threads3/8" compression braided hoses
Electrical — Battery6 V (4×AA); standby < 100 µA; pulse 0.6–0.9 A / 50–70 ms
Electrical — AC/DriverSELV 12 VDC; ≥15 VA per device suggested
Wiring Runs18–22 AWG; max 15 m at 18 AWG; low‑voltage only
Mounting & TorqueDeck 15–40 mm; shank nut 6–8 N·m; dispenser collar 2–3 N·m
Hygiene Flush12/24/48/72 h; 4–8 s; laminar flow avoids aerosolization
Thermal Purge60–70 °C for 3–5 min; coordinate with infection‑control SOPs
DispenserFoam; 1000 mL; 0.4–0.6 mL dose; foam pump with purge/prime anti‑clog
EnvironmentIP65 electronics; smooth, easy‑wipe bezels

Cyclone™ — Technical Specifications

CategorySpecification
Faucet Flow Options0.35/0.5 gpm; vandal‑resistant outlet; configurable max‑run 15–60 s
Operating Pressure20–80 psi; add arrestors near branch; avoid dead‑end runs
Inlet Threads1/2" NPSM braided hoses, 24" typical
Electrical — Battery6 V (4×AA); standby < 120 µA; pulse 0.7–1.0 A / 60–90 ms
Electrical — AC/DriverSELV 12 VDC; 20 VA per device recommended for high‑abuse sites
Wiring Runs18 AWG up to 20 m; anti‑tamper conduit where exposed
Mounting & TorqueDeck 15–45 mm; shank nut 8–10 N·m; dispenser collar 3–4 N·m; anti‑rotation gasket & locknut provided
Hygiene Flush24/48/72 h idle → 3–8 s; obstruction lockout 30–90 s
Thermal Purge60–70 °C for 3–5 min; supervised
DispenserLiquid; 1000 mL; 0.8–1.5 mL dose; anti‑drip; vandal bezel
EnvironmentIP65 electronics; abrasion‑resistant bezels; chemical‑tolerant (avoid bleach)

Nimbus™ — Technical Specifications

CategorySpecification
Faucet Flow Options0.35/0.5 gpm (laminar/aerated); slim spout geometry for counters
Operating Pressure20–80 psi; integrated pressure regulator
Inlet Threads3/8" compression braided hoses
Electrical — Battery6 V (4×AA); standby < 100 µA; pulse 0.6–0.9 A / 50–70 ms
Electrical — AC/DriverSELV 12 VDC; ≥15 VA per device
Wiring Runs18–22 AWG; up to 15 m; avoid bundling with mains
Mounting & TorqueDeck 12–35 mm; shank nut 6–7 N·m; escutcheon screws 1.0–1.2 N·m; dispenser collar 2–3 N·m
Hygiene Flush24/48 h; 3–8 s
Thermal Purge60–70 °C for 2–4 min; manual enable
DispenserLiquid; 1000 mL; 0.8–1.5 mL dose; anti‑drip; purge/prime
EnvironmentIP65; ambient 0–50 °C; RH 5–95% NC

Advanced Technical FAQ

How do I size a shared transformer for an Aero faucet + dispenser set?

Add the worst‑case VA of each device. Example (Jetstream set): faucet 12 VA peak + dispenser 10 VA peak → choose ≥25 VA SELV driver. If powering multiple sets from one driver, allow 20–30% headroom and use star (homerun) topology with 18 AWG to minimize voltage drop.

What’s the expected battery life and how do policy settings affect it?

Battery life varies with cycles/day, water temp, and policies (dwell, lockout, hygiene flush). Latching valves draw only during open/close pulses. Medium traffic (400–600 cycles/day) with hygiene flush off typically yields 12–18 months; enabling hygiene flush every 24 h reduces life ~10–15%. Prefer AC in 24/7 venues.

How can I prevent false triggers near mirrors, glossy stone, or direct daylight?

Use ToF‑assist models (Zephyr, Nimbus) and enable reflective‑surface compensation. Maintain sensor‑to‑basin offsets from the cut sheet and keep faucet–dispenser spacing at 150–250 mm (6–10 in). Avoid direct sunlight onto the sensor window or use shading trims.

What commissioning steps ensure stable hydraulics?

Flush lines before install, verify supply 20–80 psi, install hammer arrestors where required, and confirm regulator inserts (0.35/0.5 gpm). Run a leak/seat test, verify laminar stream position within 30–50 mm inside bowl’s deepest zone, and record settings via BLE snapshot (Jetstream) if available.

How do hygiene flush and thermal purge interact with mixing valves?

Hygiene flush uses tempered water for 3–8 s after selected idle periods. Thermal purge is a maintenance operation at 60–70 °C for 2–5 min; coordinate with ASSE 1070 POU mixing and facility SOPs. Use area control/signage and auto‑revert to tempered after purge.

Can I daisy‑chain power between sets?

Not recommended. Use a star topology (individual homeruns) to each set from the SELV driver to maintain voltage and isolate faults. Never share conduits with mains; keep low‑voltage separation per wiring diagram.

What soap chemistries are supported and how do I change products?

Liquid 1–3000 cP on liquid dispensers; foam pumps on Stratus only. Avoid particulates. For alcohol‑based products, confirm seal compatibility via SDS. When switching chemistries, rinse the tank and run purge/prime to clear lines.

How do I plan for vandal resistance in transit or park restrooms?

Select Cyclone or Vortex with vandal bezels, tamper‑resistant fasteners, and lockouts. Use anti‑tamper conduit for exposed low‑voltage runs. Stock regulators, seal kits, and pump modules for quick swaps.

Any EMC tips near hand dryers or VFDs?

Route low‑voltage cables away from motors and VFDs; use shielded cable where necessary and bond shields per diagram. Keep sensor windows clean; EMI can present as intermittent triggers if cable runs share trays with mains.

What finish care is recommended for PVD and Chrome?

Use non‑abrasive cleaners and microfiber. Avoid chlorine bleach and scouring pads. Test new housekeeping chemicals on a small, inconspicuous area first.

What deck thickness and basin pairing rules should I follow?

Standard decks 12–45 mm depending on model; see spec tables above. Aim the stream to land 30–50 mm inside the deepest zone of the bowl to reduce splash; laminar outlets pair best with shallow basins.

Do these devices store user data?

No personal data is stored. Optional BLE (Jetstream) is local‑first for commissioning snapshots (settings and counters). No cloud connectivity is required by default.

Note: For stamped submittals, always pull the latest cut sheet, BIM family parameters (.RFA), and wiring diagram PDF for the specific SKU and local code requirements.